PDFPrintE-mail

Dwyer-Thermal Dispersion Flow Switch-TSP2

( Dwyer )

General

The Series TDS Thermal Dispersion Flow Switch offers solid state flow detection of non-coating liquids for pump and process protection. SPDT output allows for interfacing with remote PLC or relay control device. The adjustable switch point is factory calibrated at 0.2 fps with LED indication of flow and calibration status. Units feature selectable NO or NC operation and are not damaged by over ranging flow velocities.


Features:

Service

Liquids

Wetted Materials

Polypropylene/PPS or Polyvinylidene Fluoride.

Range

0.04 to 10 fps (1.2X10-2 to 3.05 m/s)

Temperature Limits

32 to 140°F (0 to 60°C).

Pressure Limits

150 psi (10 bar) @ 25°C, derated @ 1.667 psi (.113 bar) per °C above 25°C.

Repeatability

±5% of setpoint.

Switch Type

SPDT

Electrical Rating

60 VAC/60 VDC @ 1 A.

Electrical Connections

22 AWG 3- wire, 10 ft (3 m) length.

Process Connections

3/4˝ male NPT.

Mounting Orientation

Any orientation, for pipe sizes 3/4˝ to 1-1/2˝ use 3.0˝ (7.6 cm) length switch; for 2˝ to 16˝ pipe sizes use 4.5˝ (11.4 cm) length switch.

Setpoint Adjustment

0.04 to 3 fps (1.2X10-2 to .91 m/s).

Setpoint Drift

0.5% of set point.

Response Time

1-10 seconds.

Viscosity Range

1 to 200 centipoise.

Supply Voltage

12 to 36 VDC.

Consumption:

50 mA (nominal).

Indication

LED for flow status.

Weight

3 oz (94 g).