PDFPrintE-mail
Hazardous Area Humidity Transmitter-DwyerHigh-Precision Humidity / Temperature Transmitter For HVAC

Hazardous Area Humidity/Temperature Transmitter -Dwyer

( Dwyer )
Description
Measures accurate readings of humidity & temperature in the harshest of environments. Relative Humidity Range: 0 to 100% RH with output of 4-20 mA. Temperature Range: -40 to 60°C with output of 4-20 mA.
Applications
Excellent for offshore HVAC applications, dust & grain applications.
Specifications:
Brand_Name : DWYER
Humidity_Measuring_Range : 0 to 100 %RH
Output : 4 - 20 mA
Probe : Surface / Duct Mount
Probe_Length : N.A.
Service : Suitable for harzardous area
Supply_Voltage : 9.5 to 28 VDC
Temp_Measuring_Range : -40 to 60˚C
Unit_Of_Measurement : %RH, °C,°F
Accuracy of Humidity : ± 2% (10-90% RH)
Accuracy Of Temperature : ± 0.3°C at 25°C
Hysteresis : ±1%
Repeatability : ±0.1% typical
Temperature Limits : -40 to 60°C
Storage Temperature : -40 to 80°C
Compensated Temperature : -40 to 60°C
Response Time : 15 seconds
Electrical Connections : Screw terminal block
Conduit Connection : 1/2" female NPT
Housing Material : Aluminum
Display : 2 line alpha numeric, 8 characters/line. Temperature display is °F/°C selectable
Enclosure Rating :
NEMA 4X (IP66)
FM Instrinsically Safe : Class I Div. 1 Group A, B, C, D, Class II Div. 1 Group E, F, G, Class III Div. 1 T4
Approval : FM, CE