Dwyer-Intellipoint RF Series-Intell

( Dwyer )

General

One of the Drexelbrook RF Point Level Switches You Won't Have to Calibrate

Simply install the IntelliPoint RF Series into the tank and apply power…that's it! Unlike other RF or capacitance systems that require calibration via setpoint potentiometers, jumpers, magnets, or pushbuttons, the IntelliPoint RF Series reliably detects the absence or presence of material without

any adjustments.

The IntelliPoint RF Series software continuously monitors the application for changes in composition,

dielectric or conductivity, and maintains a repeatable trip point on the probe. Other RF and capacitance

systems require calibration adjustments when the process material is changed. Since the the IntelliPoint

RF Series recognizes changes in material, it is idea for non-dedicated tanks that are used for a wide

variety of products.

Universal Power Supply

The IntelliPoint electronics use a universal power supply module that can be powered from a 85 to

250 Vac or 21 to 100 Vdc supply without moving jumpers.

Self-Test Feature

Automatic and manual test functions ensure proper system operation. An AutoVerify™ selfcheck

circuit continuously monitors that the complete system is functioning properly. The Manual Certify not only checks the function of the system, but also checks the AutoVerify self-test circuits to make sure that they are also working properly.

Dual Compartment Housing

New dual compartment housing separates the customer wiring and power supply from the sensing element and operating circuits. The encapsulated power supply/terminal block design eliminates the possibility of damage caused by moisture in the conduit.

Intelligent Electronics

• No calibration or setpoint adjustments.

• Ignores changes in dielectric or conductivity.

• Automatically recognizes and ignores coatings to prevent false alarms.

• Continuous self-test monitors circuits and sensing elements for faults.

• Universal power supply automatically detects input power source.

Diverse Applications

• Detects the absence or presence of liquids, slurries, interfaces and granulars.

Output

• (2) SPDT relays; relay#2 can be configured as an alarm or fault.

Dual Compartment Housing

• Power Supply is isolated from intrinsically-safe sensing element and circuit board.

Remote or Integral Electronics

• Unlike many technologies, electronics can be remote mounted to a convenient or safe location

 

Features:

Technology

RF Admittance

Calibration

None

Modes Of Operation

High and Low Level.

Repeatability

2 mm (0.08 inch) conductive liquids.

Response Time

less than one second

Ambient Electronic Temperature

-30 to 70°C (-28 to 158°F) KEMA.

-40 to 70°C (-40 to 158°F) FM / CSA.

Storage Temperature

-40 to 85°C (-40 to 185°F).

Indicators

LEDs: Green Power, Red Relay 1, Red Relay 2.

Self-Check

AutoVerify automatically and continuously checks electronics and sensing element for faults. Manual Certify checks that the AutoVerify circuits are functioning.

Time Delay

0-60 seconds, forward or reverse-acting.

Supply Voltage

85-250 Vac

21-100 Vdc auto-detecting without jumpers

DC to 400 Hz.

Power Consumption

2 watts maximum

Relay Contacts

(2) SPDT.

Maximum Contact Load:

5A/30 Vdc.

5A/250 Vac.

Maximum Switching Capacity:

2000 VA/150 Watt.

Minimum Contact Load (DC):

100 mA/12 Vdc.

0 to 200 mA / 12 VDC (Optional)

Housing:

Dual Compartment, Powder-Coated aluminum

with two cable entries.

Cable Entry

M20 x 1.5 CENELEC

¾-inch NPT FM/CSA.

Ingress Protection

IP66 NEMA 4X.