( Dwyer )
|
| Description | | Magnesense® Differential Pressure Transmitter with display. Measuring ranges 0.1 to 0.5 in.w.c. available with current output (4-20mA). Suitable for air & compatible gases. This compact package is loaded with features such as: field selectable English or metric ranges, field upgradeable LCD display | | Applications | | Monitors Pressure & Air Velocity. | | Specifications: | Accuracy : ± 1% F.S. Brand Name : DWYER Measuring Range : 0.1 in., 0.25 in., 0.5 in. Output : 4-20mA (2 wire) Service : Air and non-combustible, compatible gases. Supply Voltage : 10 to 35 VDC (2-wire), 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire). Unit Of Measurement : in. w.c. Temperature Limits : -18 to 66°C Pressure Limits : 1 psi max, operation, 10 psi, burst Current Consumption: 40 mA max. Response Time : Adjustable 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds. Process Connection : 3/16” ID tubing (5 mm ID). max OD 9 mm. Mounting Orientation : Diaphragm in vertical position Approvals : CE |
|
|
|
|