PDFPrintE-mail
Dwyer-Magnesense Differential Pressure TransmitterDwyer-Magnesense® Differential Pressure Transmitter

Dwyer-Magnesense Differential-Msi

( Dwyer )
Feature:
  • The Series MS Magnesense™ Differential Pressure Transmitter is an extremely versatile transmitter for monitoring pressure and air velocity. This compact package is loaded with features such as: field selectable English or metric ranges, field upgradeable LCD display, adjustable dampening of output signal (with optional display) and the ability to select a square root output for use with Pitot tubes and other similar flow sensors.
  • The magnetic sensing technology provides exceptional long term performance and enables the Magnesense™ to be the solution for a myriad of pressure and flow applications.
Specifications:
ServiceAir and non-combustible, compatible gases.
Wetted MaterialsChat with agent.
AccuracyMS-X21: 0.5˝ w.c. & 0.25˝ w.c. ±1%, 0.1˝ w.c. ±2%. 100 Pa & 50 Pa ±1%, 25 Pa ±2%. MS-X11: 5˝ & 2˝ ±1%, 1˝ w.c. ±2%. 1000 & 500 Pa ±1%, 200 Pa ±2% (@ standard conditions).
Stability±1% F.S. / year.
Temperature Limits0 to 150°F (-18 to 66°C).
Pressure Limits1 psi maximum, operation; 10 psi, burst.
Power Requirements10 to 35 VDC (2-wire); 17 to 36 VDC or isolated 21.6 to 33 VAC (3-wire).
Output Signals4 to 20 mA (2-wire); 0 to 10 V (3-wire).
Response TimeField adjustable 0.5 to 15 sec. time constant. Provides a 95% response time of 1.5 to 45 seconds.
Zero & Span AdjustmentsDigital push button.
Current Consumption40 mA max.
Display (optional)4 digit LCD.
Process Connections16˝ (5 mm) ID tubing. Maximum OD 9 mm.
Enclosure RatingNEMA 4X.
Mounting OrientationDiaphragm in Vertical position.
Weight8.0 oz (230 g).