( Dwyer )
|
| Feature: | | Series 607 Differential Pressure Transmitter combines very low ranges with exceptional stability, reliability and either ±0.25% or ±0.5% accuracy for the most demanding applications. Ranges from 0-0.1 to 0-25˝ w.c. Ultra thin glass clad silicon diaphragm design resists shock and vibration, practically eliminates drift. Certification to NIST standards is included with each unit. Tough stainless steel housing is NEMA-2 rated to protect against moisture and dirt. Use with air and other compatible gases. | | Specifications: | | Service | Air and non-combustible, compatible gases. | | Accuracy | ±0.25% or ±0.5% F.S. | | Stability | ±0.5% F.S.O./yr. | | Temperature Limits | –20 to 160˚F (–29 to 71˚C), 10 to 95% RH. | | Pressure Limits | 10 psig (0.69 bar). | | Compensated Temp. Range | 35 to 135˚F (2 to 57˚C). | | Thermal Effects | ±0.015% FS/˚F (zero and span). | | Power Requirements | 12-36 VDC. | | Output | 4 to 20 mA DC, 2-wire | | Loop Resistance | 0 to 1045 ohms Vmin=12V+[(.22A)(RL)]. | | Current Consumption | 3.6 mA (min). | | Zero and Span Adjustments | Externally accessible potentiometers, non-interactive, ±10% F.S. adjustment. | | Electrical Connections | Screw terminals. | | Process Connections | Barbed stainless steel for 3/16˝ I.D. tubing. | | Enclosure Rating | Fire retardant ABS. | | Mounting Orientation | Vertical. | | Weight | 1.04 lb (472 g). | | Housing | 300 Series SS (NEMA 2). |
|
|
|
|