| Feature: |
| Our low cost Series 668 Differential Pressure Transmitter is capable of measuring low pressures with a ±1% accuracy — ideally suited for proper building pressurization and air flow control. Transmitters can withstand up to 10 psig overpressure with no damage to the unit. Variable capacitance sensor design provides excellent sensitivity and long-term stability. Compact, lightweight design makes installation simple and easy. Units also feature reverse-polarity protection. |
| Specifications: |
| Service | Air and non-combustible, compatible gases. |
| Accuracy | ±1% of full scale (RSS) (includes non-linearity, hysteresis, and non-repeatability). |
| Temperature Limits | Operating: 0 to 150°F (-18 to 65°C), Storage: -40 to 185°F (-40 to 85°C). |
| Pressure Limits | 10 psig (0.7 kg/cm2). |
| Compensated Temp. Range | 0 to 150°F (-18 to 65°C). |
| Thermal Effects | 0.033% FS/°F (0.018% FS/°C). |
| Power Requirements | 12-30 VDC. |
| Output | 4 to 20 mA DC, 2-wire |
| Loop Resistance | 0-800 ohms. |
| Zero and Span Adjustments | ±1 mA, non-interactive. |
| Electrical Connections | Terminal strip. |
| Process Connections | 3/16˝ O.D. fitting for 1/4˝ I.D. tubing. |
| Enclosure Rating | Fire retardant ABS. |
| Weight | 3 oz (85 g). |
| Housing | Fire retardant glass filled polyester. |