| Features: |
| The Series SCZ10 has its own dual display and keypad, making process monitoring and programming a snap. The universal input allows field programming for a wide variety of sensors, making the SCZ10 one of the most flexible controls or transmitters available today. When used as a control, the SCZ10 is available with mechanical relay, switched (pulsed) DC for SSRs, or proportional current (4-20 mA) to drive motor actuators or proportional power units (SCRs). When used as a transmitter, the 4-20 mA output may be scaled virtually anywhere on the input scale, allowing for the greatest application flexibility. Features - Dual display
- Control or Transmitter
- Self-Tune and PID
- Directly Programmable from Self Contained Keypad
- Universal Input
- Compact DIN Rail Mount
|
| Specifications: |
| Inputs | Thermocouple-K, J, R, S, E, T, N, PL-II, C (W/Re5-26). |
| External Resistance | 100Ω or less. |
| B Thermocouple | External resistance: 40Ω or less. |
| RTD | Pt100, JPt100 3-wire system. Allowable input wire resistance (10Ω or less per wire). |
| DC Current | 0 to 20 mAdc, 4 to 20 mA input impedance 50Ω (50Ω shunt resistor sold separately |
| DC Voltage | 0 to 1 VDC. |
| Input Impedance | 1MΩ or greater. |
| Output Ratings |
|
| Relay Contact | 3A @ 250 VAC, Resistive; 1A @ 250 VAC Inductive (CØS =0.4), Electric life 100,000 cycles. |
| Switched Voltage (for SSR drive) | 12 VDC @ 40 mA Max. (Short-circuit protected) |
| DC Current | 4 to 20 mAdc, Load resistance: Max. 550Ω Output accuracy: ±0.3% of output span. Resolution : 12,000 counts. |
| Control Type | P, PI, PD, PID, Self Tune, On-Off, Process Retransmission. |
| Proportional Band | 0.0 to 110.0% (ON/OFF when set to 0.0). |
| Integral Time | 0 to 1000 seconds (Off when set to 0). |
| Derivative Time | 0 to 300 seconds (Off when set to 0). |
| Proportional Cycle | 1 to 120 seconds. |
| Manual Reset | Proportional band converted value. |
| Output Limit | 0 to 100% (DC current output type: -5 to 105%). |
| Hysteresis | Thermocouple and RTD Input: 0.1 to 100.0 degrees DC Voltage and Current Input: 1 to 1000 (Decimal point place follows the selection). |
| Power Requirements | 120-240 VAC, 50-60 Hz, 24 VAC 50-60 Hz optional. |
| Power Consumption | Approximately 6VA. |
| Accuracy | Thermocouple Input: ±0.2% of input span, ±1 digit or 4°F (2°C),whichever is greater. R, S input: 0 to 400°F (0 to 200°C): ±6°C (12°F). B input: 0 to 600°F (0 to 300°C): Accuracy is not guaranteed. K, J, E, N input less than 32°F (0°C): ±0.4% of input span ±1 digit. RTD Input: ±0.1% of input span ±1 digit or ±2°F (1°C), whichever is greater. DC Voltage Input: ±0.2% of input span ±1 digit. DC Current Input: ±0.2% of input span ±1 digit. |
| Input Sampling Period | 0.25 seconds, 4 Hz. |
| PV Display | Red LED 4-digit character size: 7.5 x 4.1 mm (HxW). |
| SV Display | Green LED 4-digit character size 7.5 x 4.1 mm (Hx W) |
| Display Resolution | 1 count, 1 degree, or 0.1 degree, depending on selected range. |
| Memory Backup | Nonvolatile memory, no battery used. |
| Ambient Temperature | 32 to 131°F (0 to 50°C). |
| Ambient Humidity | 35 to 85%RH (Non-condensing). |
| Weight | Approx. 5.3 oz (150 g). |
| Agency Approvals | CE, UL, cUL. |