PDFPrintE-mail
Inor-Analog 2 wire transmitter

Elecktronic-Temperature Transmitter (HVAC)

( Elecktronic )

Features

EE16 transmitters are the ideal solution for accurate measurement of relative humidity and temperature at a

reasonable price in HVAC applications. The appropriate filter cap enables employment in heavily polluted

environment. The new developed E+E humidity sensors HC101 guarantee excellent long term stability and

resistance against chemical pollutants. Their excellent reproducibility allows a simple low-cost-one-point

calibration for very good accuracy over the entire working range. EE16 transmitters are available as wall or duct mounted, with current or voltage output signals.

Typical Applications:

Building-automation

Storage rooms

Climate and ventilation control

Other Features:

Excellent price/performance ratio

Wet-table

Long term stable


Specifications

Measuring values



Relative Humidity



Sensor

HC101


Output appropriate 0...100% RH

0-10 V

-1 mA < IL < 1 mA


4-20 mA (two wire)

RL< 500 Ohm

Working range

10...95% RH


Accuracy at 20 deg C

±3% RH


Temperature dependence at 45% RH

typ. -0.05% RH/degC


Temperature



Sensor

Pt1000 (class A, DIN EN 60751)


Output appropriate 0...50 deg C

0-10 V

-1 mA < IL < 1 mA


4-20 mA (two wire)

RL< 500 Ohm

Accuracy at 20 deg C

±0.5 degC





General



Supply voltage



for 0 - 10 V

15 - 35V DC or 24V AC ±20%


for 4 - 20 mA

10V + RL x 20 mA < Uv < 35V DC


Current consumption

for DC supply typ. 8 mA



for AC supply typ. 20 mAeff


Electrical connection

screw terminals max. 1.5 mm2


Housing / protection class

Polycarbonat / IP65


Cable gland

M16


Sensor protection

membrane filter, sintered bronze filter or metal grid filter


Electromagnetic compatibility

EN 61000-6-1

EN 61326-1+A1+A2


EN 61000-6-3


Temperature range

working temperature:

-5...+50 degC


storage temperature:

-25...+60 degC