Inor-Universal HART-Compatible 2-Wire Transmitters-meso-hiInor-Universal Programmable 2 Wire

Inor-Universal Programmable 2 Wire

( Inor )

Features

IPAQ-H/-HX are universal, isolated 2-wire transmitters for temperature and other measurement applications. They combine competitive pricing, functionality and simple configuration. Useful error correction functions improve the accuracy.

• Fully universal, linearized and high-isolation

• Accepts RTD, T/C, mV and Ω

• Sensor error and system (sensor/transmitter) error correction for

highest total accuracy

• Full access to all features while in operation

• NAMUR compliant

• Consistent sensor break function

• Simplified loop check-up with calibration output

• Test output without breaking the loop (IPAQ-L)

• IPRO, easy-to-use Windows configuration software


Specifications

Input RTD

3-, 4-wire connection

 


Pt100 (α=0.00385)

-200 to +1000 °C/-328 to +1832 °F

 


Pt1000 (α=0.00385)

-200 to +200 °C/-328 to +392 °F

 


PtX 10 ≤ X ≤ 1000 (α=0.00385)

Upper range depending on X-value

 


Pt100 (α=0.003902)

-200 to +1000 °C/-328 to +1832 °F

 


Pt100 (α=0.003916)

-200 to +1000 °C/ -328 to +1832 °F

 


Ni100

-60 to +250 °C/-76 to +482 °F

 


Ni1000

-10 to +150 °C/+14 to +302 °F

 


Input Potentiometer / resistance

3-, 4-wire connection, 0 to 2000 Ω

 


Input Thermocouples

Types AE, B, E, J, K, L, N, R, S, T, U

 


Input mV

-10 to +500 mV

 


Sensor failure / Low isolation

User defi nable output

 


Adjustments - Zero

Any value within range limits

 


Adjustments - Minimum spans


 


Pt100, Pt1000, Ni100, Ni1000

10°C /18°F

 


Potentiometer

10 Ω

 


T/C, mV

2 mV

 


Output

4-20 / 20-4 mA, temperature linear

 


Operating temperature

-20 to +70°C / -40 to +185°F

 


Galvanic isolation

1500 VAC, 1 min

 


Power supply

7.5 to 36 VDC - IPAQ-H

 



8 to 30 VDC - IPAQ-HX

 


Intrinsic safety

ATEX: II 1 G EEx ia IIC (IPAQ-HX)

 


FM: Class I-III, Div. 1, Gr. A-D (IPAQ-HX)

 


Typical accuracy

±0.1 % of span

 


Connection head

Rail acc. to DIN EN50022, 35 mm